Fujitsu AIRSTAGE J-IIIL - model hasunique design and more compact that the conventional 12 HP comparable outdoor unit. Discreet installation is possible event of the roof. Airstage J-III adopts the best technology and was designed with the greatest care to provide not only energy savings and comfort but also easy installation and maintenance of equipment. The Airstage J-IIIL Heat Pump is ideal for a wide range of applications from small office buildings and stores to large houses where power supply is three phase. Top class with high COP is achieved for heat pumps by a larger heat exchanger, high efficient DC twin compressor. Watch video to learn more about some excellent product features:
Key Benefits:
Long Pipe Length - Fujitsu advanced refrigerant control technology allows to achieve a total refrigerant piping length of 400 meters. This opens up new possibilities in system design.
Non-stop Oil Recovery Operation - a comfortable room condition is maintained during oil recovery mode because the product continues to operate without stopping the cooling and heating process.
High reliability
Top Class Low Operation Sound - Top class low operation sound is realised. HIghly suited to densely populated areas thanks to their low operation sound.
DC fan motor
Large heat exchanger
Compact and high performance DC twin rotary compressor
DC inverter control
5 Years Warranty
FUJITSU AJY090LELAH 10HP OUTDOOR UNIT R410A | 3 - phase
Maximum Connectable Indoor Unit
25
Power Source
Three Phase, 380~400V , 50 Hz
Cooling Capacity
28 kW
Heating Capacity
28 kW
Cooling Input Power
8.59 kW
Heating Input Power
6.61 kW
Cooling EER
3.26 W/W
Heating COP
4.24 W/W
Air Flow Rate
9000 m3/h
Cooling Sound Pressure Level
54 dB(A)
Heating Sound Pressure Level
57 dB(A)
Min. Recommended MCB
32
Dimension (H x W x D)
1428 x 1080 x 480 mm
Weight
170 kg
Refrigerant
R410A
Charged
7.0 kg
Pipe size (Gas & Liquid)
3/8" & 3/4"
Total Pipe Length
400 m
Height difference between outdoor and indoor
40 m
MAX Height Difference
50 m
Cooling Operation
-5 0C - 46 0C
Heating Operation
-20 0C - 21 0C
Specifications are based on the following conditions
Cooling: Indoor temperature of 27 0CDB / 19 0CWD, and outdoor temperature of 35 0CDB / 24 0CWD.
Heating: Indoor temperature of 20 0CDB / 15 0CWD, and outdoor temperature of 7 0CDB / 6 0CWD.
Pipe length: 7,5 m; Height difference between outdoor unit and outdoor unit: 0 m.
The protective function may work when using it outside the operation range.